Navien · Combi boiler troubleshooting
CH series E027 air pressure sensor fault - full check
What is going on
E027 shows if the APS signal is open (about 0.1 V or less) or shorted (about 4.5 V or more) for 3 seconds, or if it already reads 1.20 V before pre-purge.
Likely causes
- APS connector loose
- Failed APS
- Bad PCB
Check in this order
- Turn off power before unplugging connectors or measuring resistance.
- The code table also says to check the vent pipe for blockage and clean the intake air filter.
- Check the APS plug is fully seated.
- APS supply is 5 V (black + white per the service table).
- Signal with fan off about 0.2-0.6 VDC. Signal with fan running: about 1-4 VDC (black-white at CN6 per the flowchart).
- Out of range = replace the APS. In range and still E027 = replace the PCB.
Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers
More combi boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.21 27 Error p.98-99. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.