Navien · Combi boiler troubleshooting

CH series E021 / E022 cold water inlet thermistor - full check

Navien CH ASME

What is going on

E021 = cold inlet sensor open (14°F or less). E022 = cold inlet sensor shorted (248°F or more). The boiler goes to safety shutdown after 3 seconds.

Likely causes

  • Loose or wet connector
  • Failed thermistor
  • Bad PCB

Check in this order

  1. Turn off power before unplugging connectors or measuring resistance.
  2. Check the plug and harness for looseness or water.
  3. Unplug from the PCB and measure the blue pair at CN13: 0.8-20 kOhm is normal.
  4. Open or 0 ohm = replace the sensor.
  5. If the sensor is good, replace the PCB.

Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.19 21 Error p.94-95; 5.20 22 Error p.96-97. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.