Navien · Combi boiler troubleshooting

CH series E016 heat exchanger high limit - full check

Navien CH ASME

What is going on

E016 locks the boiler out when the heat exchanger high limit opens at 197°F or more for 1 second. Post-purge runs. Manual reset. Wait at least 30 minutes after the trip before measuring.

Likely causes

  • Heating valves closed
  • Heating strainer plugged
  • Pump stuck or dead
  • High limit switch or thermal fuse open
  • Supply thermistor reading low
  • Heat exchanger plugged or failing

Check in this order

  1. Turn off power before unplugging connectors or measuring resistance.
  2. Check heating supply/return valves are open.
  3. Clean the heating strainer and find where the debris comes from.
  4. Check the pump runs (free the shaft, check power, capacitor, coil). No power = PCB.
  5. Wait 30 min, then check the high limit should read 0 ohm. Infinite = bad. The manual names CN13 white pair for E016 and brown pair for E030.
  6. Check the thermal fuse for continuity. If blown, replace it and find why it blew.
  7. If the supply sensor reads lower than the real water temp, replace it.
  8. Blow through the heat exchanger to check for blockage. If it trips only on hot water, check the DHW heat exchanger.
  9. Overheating surface on the heat exchanger = replace the heat exchanger.
  10. If all checks pass, replace the PCB.

Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.16 16 Error p.87-89. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.