Navien · Combi boiler troubleshooting

CH series E015 PCB error - full check

Navien CH ASME

What is going on

E015 means the board found a fault in its own circuit.

Likely causes

  • Failed PCB
  • Supply voltage out of range
  • Electrical noise on the ground

Check in this order

  1. Turn off power before unplugging connectors or measuring resistance.
  2. Measure the outlet 97-138 VAC.
  3. Press reset. If it comes back normal, watch it.
  4. Test for ground noise tape over the ground pin at the receptacle as a short test only, and see if the board behaves. Restore the ground right after.
  5. If voltage is fine and the fault stays, replace the PCB.

Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.15 15 Error p.86. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.