Navien · Combi boiler troubleshooting

CH series E013 pump - full check

Navien CH ASME

What is going on

After the pump starts, the board expects system pressure to change within 7 seconds. It tries 3 times. No change = E013, manual reset.

Likely causes

  • Pump stuck (debris in heating water)
  • No power to pump, bad start capacitor or open coil
  • Air in the piping
  • Pressure sensor not reading

Check in this order

  1. Turn off power before unplugging connectors or measuring resistance.
  2. Press reset and see if the pump runs. Pressure should rise more than 3 psi when it runs.
  3. If stuck, turn the shaft with a flat screwdriver and retry.
  4. Check pump power at CN18. Power OK: check the capacitor and coil. No power = PCB.
  5. Bleed air from the piping.
  6. Pump runs but pressure does not change = pressure sensor, then PCB.
  7. If dirty water keeps sticking the pump, clean the heating piping before fitting a new pump.

Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.13 13 Error p.84-85. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.