Navien · Combi boiler troubleshooting
CH series E013 pump - full check
What is going on
After the pump starts, the board expects system pressure to change within 7 seconds. It tries 3 times. No change = E013, manual reset.
Likely causes
- Pump stuck (debris in heating water)
- No power to pump, bad start capacitor or open coil
- Air in the piping
- Pressure sensor not reading
Check in this order
- Turn off power before unplugging connectors or measuring resistance.
- Press reset and see if the pump runs. Pressure should rise more than 3 psi when it runs.
- If stuck, turn the shaft with a flat screwdriver and retry.
- Check pump power at CN18. Power OK: check the capacitor and coil. No power = PCB.
- Bleed air from the piping.
- Pump runs but pressure does not change = pressure sensor, then PCB.
- If dirty water keeps sticking the pump, clean the heating piping before fitting a new pump.
Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers
More combi boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.13 13 Error p.84-85. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.