Navien · Combi boiler troubleshooting

CH series E012 flame loss - full check

Navien CH ASME

What is going on

If the flame drops out during a burn, the unit relights and counts. After 20 flame losses in a row it shows E012, manual reset.

Likely causes

  • Low gas pressure (LP drops in winter), small pipe or meter
  • Gas-air differential out at 3-stage min
  • Wrong DIP capacity setting
  • Air pressure sensor reading high
  • Dirty nozzles (stage 2/3 cause dropouts when stages switch)
  • Multi-stage valve or main valve proportional part faulty
  • Bad PCB

Check in this order

  1. Gas work licensed gas tech only. Turn off gas and power before opening the gas train, and leak-test every joint you opened.
  2. Inlet pressure at max fire NG 6-10.5 in. W.C, LP 8-13.5 in. W.C. Check dynamic pressure.
  3. Gas pipe 3/4 in. or larger. Check gas meter size and the inlet fitting gasket.
  4. Check the gas-air differential at 3-stage min (DIP 1 and 2 ON). Try the adjusting screw under the gas valve half a turn and watch the flame.
  5. Check the DIP capacity setting.
  6. Pull the manifold and clean the nozzles.
  7. Flame drops when stages switch check the multi-stage valve.
  8. Replace the air pressure sensor if it reads high.
  9. If all checks pass, replace the PCB.

Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.13 12 Error p.82-83. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.