Navien · Combi boiler troubleshooting
CH series E011 high water pressure - full check
What is going on
E011 shows when system pressure stays at 56.6 psi or more for 3 seconds. It clears at 43.5 psi or less. If the boiler display shows SEE with E011 on the room controller, the pressure sensor itself has failed.
Likely causes
- Expansion tank failed or waterlogged
- System overfilled
- Relief valve stuck
- Pressure sensor frozen or failed (SEE)
Check in this order
- Check system pressure with a gauge. Over about 3.9 bar (56.6 psi) is real high pressure.
- Check the expansion tank charge.
- Do not overfill when topping up. Drain to normal pressure.
- Check the relief valve is not stuck.
- E011 + SEE check if the sensor froze. Check the sensor plug for open or short. Replace the pressure sensor if bad.
Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers
More combi boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.12 11 Error p.81-82. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.