Navien · Combi boiler troubleshooting

CH series E010 air pressure (APS) - full check

Navien CH ASME

What is going on

During pre-purge, E010 shows if the air pressure sensor never reaches ignition level after 5 tries (lockout). While firing, it shows if fan RPM runs 1,000 or more above target (shutdown, fan keeps running). It clears when RPM comes back within ±500.

Likely causes

  • APS hose torn, plugged or holding water
  • Venturi/burner hole plugged with soot
  • Condensate hose or trap blocked or frozen
  • Intake or exhaust blocked, dented, or holding rainwater
  • Exhaust being pulled back into the intake
  • Weak fan
  • Bad APS or PCB

Check in this order

  1. Turn off power before unplugging connectors or measuring resistance.
  2. Check the APS hose for tears and water. Blow through it to check it is clear.
  3. Check the venturi hole for soot or debris.
  4. Check the condensate hose is not kinked or frozen. Pull the trap bottom and clear it.
  5. Check intake and exhaust pipes for dents, blockage and water (pipe sloping the wrong way).
  6. Check intake/exhaust spacing. Exhaust re-entering the intake causes noise and unstable APS/RPM.
  7. APS power 4.5-5.5 VDC black to red at CN6. APS signal: 0.3-4.0 VDC black to white. Bad readings = replace APS.
  8. Very low fan RPM = replace the fan.
  9. If all checks pass, replace the APS, then the PCB.

Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.11 10 Error p.78-80. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.