CH series E009 fan motor RPM - full check

Navien CH ASME

What is going on

E009 shows when the fan RPM signal is 400 or less: during pre-purge (after 10 tries) or for 3 seconds while firing. The boiler locks out.

Likely causes

  • No power to the fan from the PCB
  • Fan motor weak or failed
  • Wet fan connector
  • Loose white connector on the PCB

Check in this order

  1. Turn off power before unplugging connectors or measuring resistance.
  2. Fan power 120-180 VDC between black and red at CN8 (manual also gives 127-184 VDC). No power = PCB.
  3. Fan signal 2-8 VDC between black and white at CN8 while running. Power OK but no signal or very low RPM = replace the fan.
  4. Check the fan plug for water. Fix the leak and dry it.
  5. Check the white connector on the PCB is seated.
  6. When refitting a fan, do not overtighten the screws with a drill (cracks the housing).

Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.10 09 Error p.75-77; 8.2.4 p.122. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.