CH series E005 / E006 heating supply thermistor - full check
What is going on
E005 = supply sensor open (reads 14°F or less). E006 = supply sensor shorted (reads 248°F or more). Both trigger after 3 seconds.
Likely causes
- Loose or wet connector
- Failed thermistor
- Bad PCB
Check in this order
- Turn off power before unplugging connectors or measuring resistance.
- Check the sensor plug at the thermistor and at CN13. Look for water on the plug or harness (leaks).
- Unplug from the PCB and measure normal is 0.8-20 kOhm. Open (E005) or 0 ohm (E006) = replace the sensor.
- Check the displayed heating temp against the real pipe temp.
- If the sensor is good, replace the PCB.
Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers
More combi boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.6 05 Error p.71; 5.7 06 Error p.72. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.