Navien · Combi boiler troubleshooting

CH series E005 / E006 heating supply thermistor - full check

Navien CH ASME

What is going on

E005 = supply sensor open (reads 14°F or less). E006 = supply sensor shorted (reads 248°F or more). Both trigger after 3 seconds.

Likely causes

  • Loose or wet connector
  • Failed thermistor
  • Bad PCB

Check in this order

  1. Turn off power before unplugging connectors or measuring resistance.
  2. Check the sensor plug at the thermistor and at CN13. Look for water on the plug or harness (leaks).
  3. Unplug from the PCB and measure normal is 0.8-20 kOhm. Open (E005) or 0 ohm (E006) = replace the sensor.
  4. Check the displayed heating temp against the real pipe temp.
  5. If the sensor is good, replace the PCB.

Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.6 05 Error p.71; 5.7 06 Error p.72. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.