Navien · Air conditioner troubleshooting

Sensor and valve functions on the outdoor unit

NAA

What is going on

Quick reference for what each outdoor sensor and valve is used for. T3 is the outdoor coil temperature, used for high-temperature protection and outdoor fan control. T4 is the outdoor ambient temperature, used to limit maximum compressor frequency. T5 is the compressor discharge temperature, used for high-discharge and low-superheat protection. T7 is the control board pipe temperature, used for condensation prevention. Tfin is the IPM (inverter module) temperature, used for high IPM temperature protection. PT is the pressure transducer, which senses evaporating pressure and is used for compressor frequency control and low-pressure protection. The pressure equalizer valve (PEV) balances system pressure before compressor start-up.

Applies to: NAA outdoor unit

More air conditioner guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NAA air conditioner service manual, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.