Navien · Air conditioner troubleshooting
Replace accumulator
What is going on
The accumulator is brazed into the suction and discharge lines. Recover refrigerant before cutting.
Check in this order
- Turn off the circuit breaker.
- Remove the 10 top cover screws and the 10 screws on the top and bottom side panels, then remove the top cover and panels.
- Recover all refrigerant from the refrigerant circuit before any heat work.
- Braze apart the suction and discharge pipe sections with a torch.
- Install the new accumulator in the unit.
- Remove the rubber caps from the new accumulator's suction and discharge pipes to release the nitrogen.
- Braze the suction and discharge pipes to the compressor with a torch.
- Evacuate the system.
- After vacuuming, open the service valves. If a recovery unit is used, charge refrigerant.
Applies to: NAA17V36 and NAA17V60
More air conditioner guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NAA air conditioner service manual, p. 52-53. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.