PCB detects overcurrent
What is going on
The PCB detected compressor or system current above the protection threshold. No code number is printed for this fault on these pages.
Likely causes
- Defective compressor or system
Check in this order
- Use a clamp meter to measure the AC current to the compressor.
- Compare the reading with the check value for this model on item 20 of the PCB.
- If the difference between the clamp meter reading and the check value is more than ±10%, the compressor or system has a fault.
- If the difference is large, replace the PCB.
- Check that the motor and compressor wiring is tight.
- Check the system for restrictions and refrigerant charge.
Applies to: NAA17V36-24K/36K, NAA17V60-48K/60K
More air conditioner guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NAA air conditioner service manual, p. 32. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.