Navien · Air conditioner troubleshooting

Check for air or nitrogen contamination in the system

NAA Series

What is going on

Method to tell whether non-condensable gas is in the refrigerant circuit.

Likely causes

  • Air or nitrogen left in the system after service
  • Non-condensable gas raising high-side pressure

Check in this order

  1. Run the system until stable, about 10 to 15 minutes.
  2. Measure the high-side pressure and the condensing temperature.
  3. Look up the condensing temperature on the refrigerant P-T chart to get the saturation pressure.
  4. Compare the measured pressure with the saturation pressure.
  5. If the measured pressure is much higher than saturation pressure, air or nitrogen is likely present. Evacuate, refill refrigerant and add refrigeration oil.

Applies to: NAA17V36-24K/36K, NAA17V60-48K/60K

More air conditioner guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NAA air conditioner service manual, p. 34. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.