Navien · Air conditioner troubleshooting
Check for air or nitrogen contamination in the system
What is going on
Method to tell whether non-condensable gas is in the refrigerant circuit.
Likely causes
- Air or nitrogen left in the system after service
- Non-condensable gas raising high-side pressure
Check in this order
- Run the system until stable, about 10 to 15 minutes.
- Measure the high-side pressure and the condensing temperature.
- Look up the condensing temperature on the refrigerant P-T chart to get the saturation pressure.
- Compare the measured pressure with the saturation pressure.
- If the measured pressure is much higher than saturation pressure, air or nitrogen is likely present. Evacuate, refill refrigerant and add refrigeration oil.
Applies to: NAA17V36-24K/36K, NAA17V60-48K/60K
More air conditioner guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NAA air conditioner service manual, p. 34. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.