Navien · Air conditioner troubleshooting

Replace compressor

NAA

What is going on

The compressor is replaced by recovering refrigerant, cutting the pipes, fitting a new compressor, brazing, evacuating and recharging.

Check in this order

  1. Turn off the circuit breaker.
  2. Remove the 10 top cover screws and the 10 screws on the top and bottom side panels, then remove the top cover and panels.
  3. Remove the compressor sound blanket.
  4. Recover all refrigerant from the refrigerant circuit before any heat work.
  5. Disconnect the faston connectors from compressor terminals U, V and W. Note their positions first.
  6. Braze off the suction and discharge pipes with a torch.
  7. Remove the 3 nuts in the rubber pad section and lift the faulty compressor out.
  8. Install the new compressor. Insert the rubber pads before tightening the fixing nut.
  9. Remove the rubber caps from the new compressor's suction and discharge pipes to release the nitrogen.
  10. Braze the suction and discharge pipes to the compressor.
  11. Connect the power cable to the compressor terminal board and fit the sound-proof covering.
  12. Evacuate the unit with a vacuum pump down to 350 microns.
  13. After vacuuming, open the service valves. If a recovery unit is used, charge refrigerant.

Applies to: NAA17V36 and NAA17V60

More air conditioner guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NAA air conditioner service manual, p. 51-52. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.