Navien · Air conditioner troubleshooting

Compressor discharge temperature protection (T5)

NAA

What is going on

If compressor discharge temperature T5 goes above its set maximum, the unit stops until T5 reaches the recovery temperature of 194 F (90 C). The unit restarts when T5 is below the recovery temperature of 194 F (90 C). The manual does not print the numeric set maximum on this page.

Likely causes

  • High discharge temperature, possibly from low refrigerant charge, restriction, or low superheat

Check in this order

  1. Check T5 reading on the parameter check table.
  2. Check refrigerant charge and superheat readings.
  3. Restart is automatic once T5 falls to the recovery point.

Applies to: NAA outdoor unit

More air conditioner guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NAA air conditioner service manual, p. 17. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.