Compressor discharge temperature protection (T5)
What is going on
If compressor discharge temperature T5 goes above its set maximum, the unit stops until T5 reaches the recovery temperature of 194 F (90 C). The unit restarts when T5 is below the recovery temperature of 194 F (90 C). The manual does not print the numeric set maximum on this page.
Likely causes
- High discharge temperature, possibly from low refrigerant charge, restriction, or low superheat
Check in this order
- Check T5 reading on the parameter check table.
- Check refrigerant charge and superheat readings.
- Restart is automatic once T5 falls to the recovery point.
Applies to: NAA outdoor unit
More air conditioner guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NAA air conditioner service manual, p. 17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.