Navien · Air conditioner troubleshooting
Outdoor coil high-temperature protection (T3)
What is going on
If T3 goes above the maximum set temperature of 147 F (64 C), the unit stops and waits until T3 falls to the recovery point. The unit restarts when T3 drops below the set recovery temperature of 135 F (57 C).
Likely causes
- Outdoor coil running too hot, often from poor airflow or heat load at the condenser
Check in this order
- Check outdoor coil and fan for blockage or poor airflow.
- Confirm T3 reading on the parameter check table.
- Restart is automatic once T3 falls below 135 F (57 C).
Applies to: NAA outdoor unit
More air conditioner guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NAA air conditioner service manual, p. 17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.