Replace refrigerant pressure sensor

NAA

What is going on

The pressure sensor is brazed into the refrigerant circuit. The refrigerant must be recovered first and fire precautions apply during brazing.

Check in this order

  1. Turn off the circuit breaker.
  2. Remove the 10 top cover screws and the 10 screws on the top and bottom side panels, then remove the top cover and panels.
  3. Recover all refrigerant from the refrigerant circuit before any heat work.
  4. Disconnect the wiring connectors from the PCB.
  5. Disconnect the pressure sensor connector.
  6. Wrap a wet cloth around the components near the sensor.
  7. Heat the brazing point of the sensor pipe with a torch and use pliers to pull the sensor pipe off the refrigerant pipe. The pipe can also be cut and the remaining stub heated off.
  8. To install remove the plug or cap and make sure the pipe is clean.
  9. Install the sensor in the correct location.
  10. Wrap a wet cloth around the sensor and nearby parts, keep a nitrogen purge running, then braze the sensor pipe to the refrigerant pipe.
  11. Route the sensor harness to the PCB and connect the sensor connector.
  12. Secure the harness with new cable ties.
  13. Pull a vacuum on the system, then add refrigerant.

Applies to: NAA17V36 and NAA17V60

More air conditioner guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NAA air conditioner service manual, p. 49-50. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.