Replace refrigerant high pressure switch

NAA

What is going on

The high pressure switch is brazed into the refrigerant line. Recover refrigerant before heating the joint.

Check in this order

  1. Turn off the circuit breaker.
  2. Remove the 10 top cover screws and the 10 screws on the top and bottom side panels, then remove the top cover and panels.
  3. Recover all refrigerant from the refrigerant circuit before any heat work.
  4. Disconnect the wiring connectors from the PCB.
  5. Wrap a wet cloth around the components near the switch.
  6. Heat the brazing point of the switch pipe with a torch and use pliers to remove the switch pipe from the refrigerant pipe.
  7. To install remove the plug or cap and make sure the pipe is clean.
  8. Install the switch in the correct location.
  9. Wrap a wet cloth around the switch and nearby parts, then braze the switch pipe to the refrigerant pipe.
  10. Route the harness to the PCB and connect it.
  11. Add refrigerant to the refrigerant circuit.

Applies to: NAA17V36 and NAA17V60

More air conditioner guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NAA air conditioner service manual, p. 50-51. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.