Replace outdoor temperature sensor (T3, T4, T5, T7)

NAA

What is going on

Sensors are replaced in the outdoor unit. Check the sensor against the user interface before replacing it, because a bad PCB can also show a wrong temperature.

Likely causes

  • Sensor reads a temperature that does not match the resistance of the sensor

Check in this order

  1. Turn off the circuit breaker for the unit.
  2. Remove the 10 top cover screws and the 18 bottom cover screws, then take off the upper covers and side panels.
  3. Pull the clip that holds the thermistor.
  4. Lift the thermistor out of its holder.
  5. Unplug the thermistor connector from the PCB and remove the sensor.
  6. Before replacing, compare the measured resistance with the temperature shown on the user interface. If the resistance matches but the displayed temperature is wrong, replace the PCB instead.

Applies to: NAA17V36-24K/36K, NAA17V60-48K/60K

More air conditioner guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NAA air conditioner service manual, p. 48. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.