Daikin · Air conditioner troubleshooting

Remove thermistors and insulation tube on AC models

DX6VS

What is going on

AC 1.5 to 3.0 ton units. Remove the outdoor air, outdoor coil and pipe thermistors, detach the OL relay and HPS connectors, and remove the insulation tube.

Check in this order

  1. Remove the outdoor air thermistor and the outdoor coil thermistor.
  2. Remove the suction pipe, discharge pipe and liquid pipe thermistors.
  3. Detach the OL relay connector and the HPS connectors.
  4. Cut the 2 clamps and remove the insulation tube from the suction pipe thermistor.
  5. When reassembling, keep the lead wires from touching the edges.
  6. When reassembling, face the slit in the insulation tube away from the suction pipe thermistor.

Applies to: 1.5 to 3.0 ton AC models

More air conditioner guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin sm-sius612209ea service instructions, pp. 92-93. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.