Check capacitor DC voltage before servicing (1.5 to 5.0 ton outdoor units)

DX6VS / DZ6VS

What is going on

Confirm the capacitor is discharged before touching it. The voltage between the C+ and C- terminals must read 50 V DC or less. Page text for the procedure steps is partly garbled in this copy, so verify against the full manual before work.

Check in this order

  1. Turn off power to the unit and wait about 10 minutes.
  2. Set a multimeter to the DC voltage range.
  3. Measure across C+ and C- on the capacitor.
  4. Proceed only if the reading is 50 V DC or less. Otherwise, discharge the capacitor as the manual directs before continuing.

Applies to: 1.5 to 3.0 ton and 3.5 to 5.0 ton outdoor units

More air conditioner guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 5-6. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.