Daikin · Air conditioner troubleshooting

Cooling analysis: possible causes and remedies

DX6VSDZ6VS

What is going on

Use the cooling analysis chart when readings fall outside the listed thresholds. Marked symptoms show which causes to check.

Likely causes

  • Liquid or gas stop valve not fully open
  • Line set restriction or line set too long
  • Blocked filter-dryer
  • Indoor EEV coil or EEV failure
  • Outdoor solenoid valve coil or valve failure
  • High pressure switch failure
  • Pressure sensor failure
  • Outdoor suction, discharge, coil or air thermistor failure
  • Outdoor or indoor air recirculation
  • Dirty outdoor or indoor heat exchanger
  • Outdoor or indoor ambient/return air temperature out of range
  • Non-condensable gas in system
  • Outdoor fan motor failure
  • Overcharge or undercharge of refrigerant; leak
  • Outdoor control board failure; indoor unit failure
  • Compressor failure
  • Low indoor CFM

Check in this order

  1. Fully open the liquid stop valve and gas stop valve.
  2. Check the line set for restrictions and length; change outdoor position if needed.
  3. Replace the filter-dryer if blocked.
  4. Check indoor and outdoor EEV coil connections and EEV operation; repair or replace as needed.
  5. Check the outdoor solenoid valve coil and valve; repair or replace as needed.
  6. Check high pressure switch resistance; replace if needed.
  7. Check pressure sensor resistance and connections; replace if needed.
  8. Check thermistor resistance and connections; replace if needed.
  9. Re-arrange outdoor or indoor unit position to stop recirculation.
  10. Clean outdoor or indoor heat exchanger.
  11. Recover refrigerant, evacuate the pipe and recharge if non-condensable gas is present.
  12. Replace outdoor fan motor if failed.
  13. Recover part of charge if overcharged; test for leaks and add refrigerant if undercharged.
  14. Find and repair the leak point.
  15. Replace outdoor control board if failed; replace indoor unit or compressor if failed.
  16. Check airflow trim and indoor fan motor; repair or replace as needed.

Applies to: DX6VS/DZ6VS outdoor units in cooling

More air conditioner guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin SiUS612209EB service instructions, p. 12. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.