Daikin · Air conditioner troubleshooting
Remove heat exchanger - AC models, 3.5 to 5.0 ton
What is going on
Heat exchanger and partition plate removal on AC-only outdoor units.
Check in this order
- Remove the 3 screws holding the rear cover and remove the cover.
- Heat the brazed joints of the heat exchanger and disconnect them. Protect nearby plastic and putty as noted in the manual.
- Remove the 2 screws holding the heat exchanger and lift it out.
- Remove the partition plate. On 4-screw models remove 4 screws; on 3-screw models remove 3 screws.
- On reassembly, insert the hook on the bottom frame into the slit in the partition plate.
Applies to: 3.5 to 5.0 ton AC outdoor units
More air conditioner guides
- AC model wiring removal: PS connector, compressor leads and outdoor thermistors
- Check capacitor DC voltage before servicing (1.5 to 5.0 ton outdoor units)
- Clean or replace the titanium apatite deodorizing filters
- Clean the air filters
- Connect the wireless LAN adapter using WPS
- Connect the wireless LAN adapter without WPS
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 126-127. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.