Daikin · Air conditioner troubleshooting
Remove compressor - AC models, 3.5 to 5.0 ton
What is going on
Access and removal sequence for the compressor on AC-only outdoor units.
Check in this order
- Remove the 6 screws holding the stop valve mounting plate and set the plate aside. Use the same screws when reassembling (marked M5 x 16, 3-class hex head tapping screws). If a conduit tube is attached to the plate, remove it first.
- Remove the top sound blanket, then the body sound blanket.
- Remove the terminal cover.
- Disconnect the compressor lead wires. Wire colours are U red, V yellow, W blue. The wiring differs by model, so connect the leads exactly as shown in the manual on reassembly.
- Remove the overload (OL) device. When refitting, hook the lower tabs of the retainer into the fixture's square holes first, then push the upper hooks until they latch.
- Heat the brazed compressor piping joints and disconnect them. Protect nearby parts with a sheet or steel plate.
- Remove the 2 nuts that secure the compressor.
Applies to: 3.5 to 5.0 ton AC outdoor units
More air conditioner guides
- AC model wiring removal: PS connector, compressor leads and outdoor thermistors
- Check capacitor DC voltage before servicing (1.5 to 5.0 ton outdoor units)
- Clean or replace the titanium apatite deodorizing filters
- Clean the air filters
- Connect the wireless LAN adapter using WPS
- Connect the wireless LAN adapter without WPS
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 121-123. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.