Daikin · Air conditioner troubleshooting
Remove compressor, AC models 3.5 to 5.0 ton
What is going on
Air conditioner models only. Work from the stop valve plate and sound blankets down to the compressor mounting nuts.
Check in this order
- Remove the 6 screws and take off the stop valve mounting plate. The circled screws are 3-class hex head tapping screws (M5 x 16); reuse the same screws when reassembling.
- If a conduit tube is connected to the stop valve plate, remove it.
- Remove the top sound blanket, then the body sound blanket.
- Remove the terminal cover. The 5.0 ton model is shown as the representative drawing.
- Disconnect the compressor lead wires. Wiring differs by model: U is red, V is yellow, W is blue. Reconnect them exactly as shown when reassembling.
- Remove the OL. When reassembling, fit the retainer as described in the manual and route the OL lead wire through the harness path.
- Protect the area from the brazing flame as with the other procedures.
- Heat the brazed compressor piping joints and disconnect them.
- Remove the 2 nuts that secure the compressor.
Applies to: DX6VS / DZ6VS air conditioner outdoor units, 3.5 to 5.0 ton
More air conditioner guides
- AC model wiring removal: PS connector, compressor leads and outdoor thermistors
- Check capacitor DC voltage before servicing (1.5 to 5.0 ton outdoor units)
- Clean or replace the titanium apatite deodorizing filters
- Clean the air filters
- Connect the wireless LAN adapter using WPS
- Connect the wireless LAN adapter without WPS
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, pp. 121 to 123. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.