Daikin · Air conditioner troubleshooting
Outdoor unit wiring removal (AC models)
What is going on
Disconnects compressor, pressure switch and sensor wiring on AC models.
Check in this order
- Disconnect the PS connector (X17A).
- Disconnect the compressor connectors (U, V, W) and release the lead wires from the hooks.
- Remove the outdoor air thermistor.
- Remove the outdoor coil thermistor.
- Remove the insulation tube and suction pipe thermistor as described for the HP unit, using the same slit alignment on reassembly.
- Remove the discharge pipe thermistor, liquid pipe thermistor and ground wire.
- Detach the OL relay connector.
Applies to: 3.5 to 5.0 ton AC models
More air conditioner guides
- AC model wiring removal: PS connector, compressor leads and outdoor thermistors
- Check capacitor DC voltage before servicing (1.5 to 5.0 ton outdoor units)
- Clean or replace the titanium apatite deodorizing filters
- Clean the air filters
- Connect the wireless LAN adapter using WPS
- Connect the wireless LAN adapter without WPS
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin SiUS612209EB service instructions, p. 114-115. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.