Disconnect outdoor wiring on AC units (1.5 to 3.0 ton)
What is going on
Removal sequence for outdoor wiring, thermistors and pipe sensors on 1.5 to 3.0 ton cooling-only models.
Check in this order
- Cut the 4 clamps and disconnect the PS lead wire at connector X840A. On reassembly, fix the lead to the same position with new clamps.
- Remove the 3 clamps and disconnect the compressor lead wire at the U, V, W connector.
- Remove the outdoor air thermistor and outdoor coil thermistor. On reassembly, route the lead wires so they do not touch sharp edges.
- Remove the suction pipe, discharge pipe and liquid pipe thermistors. Detach the OL (overload protector) relay connector and the HPS connectors. Cut the 2 clamps and remove the insulation tube.
- On reassembly, position the slit of the insulation tube opposite the suction pipe thermistor.
Applies to: DX6VS / DZ6VS AC outdoor units, 1.5 to 3.0 ton
More air conditioner guides
- AC model wiring removal: PS connector, compressor leads and outdoor thermistors
- Check capacitor DC voltage before servicing (1.5 to 5.0 ton outdoor units)
- Clean or replace the titanium apatite deodorizing filters
- Clean the air filters
- Connect the wireless LAN adapter using WPS
- Connect the wireless LAN adapter without WPS
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 91-92. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.