Weil-McLain · Boiler

LOW WTR CONDITION Integrated LWCO sees no water

Critical severity SVF 500/600 Series 1

What the control is telling you

Occurs if the integrated low water cut-off sees no water. Manual reset of the control is needed if the contacts are open.

Applies to: SVF 500/600 Series 1 boiler

Likely causes

  • Low water condition in the system
  • Stuck LWCO test button
  • Wiring fault between LWCO and control
  • Fouled LWCO probe
  • Failed LWCO

Test and repair steps

  1. Check for a low water condition in the system and repair as needed; see the water piping section starting on page 19
  2. Check whether the LWCO test button is stuck; if so, replace the control
  3. If no low water condition exists, check Diagnostics -> Inputs to see LWCO status
  4. If LWCO shows OPEN, check wiring between the LWCO and the control
  5. If wiring is fine, remove the LWCO and clean the probe
  6. If the problem still exists, replace the LWCO

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: SVF 500/600 Series 1 boiler manual, p. 129. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.