Weil-McLain · Boiler

IGNITION 1 FAULT Ignition attempt failed: no flame sensed

High severity SVF 500/600 Series 1

What the control is telling you

The boiler made two ignition attempts and either never detected flame, or flame sense never reached the 0.8 proof-of-flame threshold within 2 seconds. Reset from the manual reset screen.

Applies to: SVF 500/600 Series 1 boiler

Likely causes

  • Condensate trap blocked, letting condensate build up inside the heat exchanger
  • Loose or bad ignition cable connection

Test and repair steps

  1. Check the condensate trap for a blockage that lets condensate collect inside the heat exchanger
  2. Check the ignition cable connection
  3. Reset using the manual reset screen on the display

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: SVF 500/600 Series 1 boiler manual, p. 128. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.