Weil-McLain · Boiler
IGNITION 1 FAULT Ignition attempt failed: no flame sensed
What the control is telling you
The boiler made two ignition attempts and either never detected flame, or flame sense never reached the 0.8 proof-of-flame threshold within 2 seconds. Reset from the manual reset screen.
Applies to: SVF 500/600 Series 1 boiler
Likely causes
- Condensate trap blocked, letting condensate build up inside the heat exchanger
- Loose or bad ignition cable connection
Test and repair steps
- Check the condensate trap for a blockage that lets condensate collect inside the heat exchanger
- Check the ignition cable connection
- Reset using the manual reset screen on the display
Other codes on the same units
- IGNITION 2 FAULT Flame not established at running threshold
- Internal Clock Fault Control internal clock out of sync
- LOW FLAME SHUTDOWN Flame quality dropped below running threshold
- LOW WTR CONDITION Integrated LWCO sees no water
- LOW WTR CUTOFF WARNING LWCO probe needs cleaning
- Target Reduced – Boiler Target reduced: boiler outlet near max temperature
- Target Reduced – Flow Target reduced: low water flow across heat exchanger
- Target Reduced – Flue Target reduced: flue temperature 200-210°F
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: SVF 500/600 Series 1 boiler manual, p. 128. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.