Weil-McLain · Boiler
IGNITION 2 FAULT Flame not established at running threshold
What the control is telling you
The boiler made two ignition attempts and did not reach the running flame threshold for its model within 10 seconds. Reset from the manual reset screen.
Applies to: SVF 500/600 Series 1 boiler
Likely causes
- Fouled, worn, bent or faulty igniter
- Dirty burner or heat exchanger causing high back pressure and poor ignition
- Flue gas recirculation (brown or black deposits on igniter)
- Incorrect gas pressure or combustion settings
- Flue or intake pipe restriction or blockage
- Burner fasteners or gaskets faulty
- Venturi gaskets faulty or wrong venturi (propane models use different venturis)
- Wrong boiler model selected in control, or high altitude not selected above 5,500 ft
- Ignition cable resistance out of range
Test and repair steps
- Clean a fouled ignition electrode with steel wool; replace a worn or badly fouled electrode with the proper repair part
- Set igniter rods parallel with a 3.5 mm (0.138 in.) spark gap
- Thin white deposits on the igniter are normal; brown or black deposits mean flue gas recirculation, so thoroughly inspect the venting system and termination for leakage or flue gas feedback into the air line
- Clean the burner and heat exchanger per the instructions starting on page 110; visual inspection of flue ways may not be enough
- Check combustion settings on high and low fire and adjust per setup instructions if needed; check flame signal during combustion testing (page 115)
- Check incoming gas pressure with the boiler off and at high fire; adjust within the limits on the rating label
- Verify the correct boiler model is selected in the control and high altitude is selected for installs 5,500 ft or more above sea level
- Check that ignition cable resistance measures 1000 Ohms (+/- 50 Ohms)
- Check flue pipe and intake pipe for restrictions or blockage
- Check burner fasteners and gaskets
- Check venturi gaskets and confirm the correct venturi is installed
Other codes on the same units
- IGNITION 1 FAULT Ignition attempt failed: no flame sensed
- Internal Clock Fault Control internal clock out of sync
- LOW FLAME SHUTDOWN Flame quality dropped below running threshold
- LOW WTR CONDITION Integrated LWCO sees no water
- LOW WTR CUTOFF WARNING LWCO probe needs cleaning
- Target Reduced – Boiler Target reduced: boiler outlet near max temperature
- Target Reduced – Flow Target reduced: low water flow across heat exchanger
- Target Reduced – Flue Target reduced: flue temperature 200-210°F
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: SVF 500/600 Series 1 boiler manual, p. 128. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.