Weil-McLain · Boiler
LOW FLAME SHUTDOWN Flame quality dropped below running threshold
What the control is telling you
Flame quality dropped below the allowable running flame threshold but the flame did not go out. Clears automatically when pre-purge is reached.
Applies to: SVF 500/600 Series 1 boiler
Likely causes
- Fouled, worn, bent or faulty igniter
- Dirty burner or heat exchanger causing high back pressure
- Flue gas recirculation
- Incorrect gas pressure or combustion settings
- Flue or intake restriction
- Burner fasteners or gaskets faulty
- Venturi gaskets faulty or wrong venturi
- Wrong model or altitude setting in the control
- Ignition cable resistance out of range
Test and repair steps
- Clean a fouled ignition electrode with steel wool; replace a worn or badly fouled electrode
- Set igniter rods parallel with a 3.5 mm (0.138 in.) spark gap
- Brown or black igniter deposits point to flue gas recirculation; inspect the venting system and termination for leakage or feedback into the air line
- Clean the burner and heat exchanger per page 110
- Check combustion settings on high and low fire and adjust if needed; check flame signal (page 115)
- Check incoming gas pressure with the boiler off and at high fire; adjust within rating label limits
- Verify the correct model and high altitude setting are selected in the control
- Check that ignition cable resistance measures 1000 Ohms (+/- 50 Ohms)
- Check flue and intake pipes for restrictions or blockage
- Check burner fasteners and gaskets
- Check venturi gaskets and confirm the correct venturi (propane models use different venturis)
Other codes on the same units
- IGNITION 1 FAULT Ignition attempt failed: no flame sensed
- IGNITION 2 FAULT Flame not established at running threshold
- Internal Clock Fault Control internal clock out of sync
- LOW WTR CONDITION Integrated LWCO sees no water
- LOW WTR CUTOFF WARNING LWCO probe needs cleaning
- Target Reduced – Boiler Target reduced: boiler outlet near max temperature
- Target Reduced – Flow Target reduced: low water flow across heat exchanger
- Target Reduced – Flue Target reduced: flue temperature 200-210°F
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: SVF 500/600 Series 1 boiler manual, p. 129. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.