Weil-McLain · Boiler
AIR PRESSURE Switch Open Air pressure switch open
What the control is telling you
Air pressure connection is open. The switch is closed in normal operation. High exhaust pressure or high intake/cabinet vacuum opens the switch. Reset from the manual reset screen.
Applies to: SlimFit 1000-2000 Series 2
Likely causes
- Exhaust or intake restriction
- Blocked condensate drain
- Wrong boiler size selected in control
- Loose P7 connection or pressure switch connections
Test and repair steps
- Check boiler size selected in control against the rating label and correct if needed.
- Check exhaust and intake pipes for restrictions or blockage.
- Check the condensate drain; clean the base collection area and trap, then refill trap with fresh water.
- Check the P7 connection (see Figures 52 and 53, pages 48 and 50).
- Check the connections on the pressure switch.
Other codes on the same units
- Closure Switch Fault Closure switch open on P7 pins 2 and 3
- DISPLAY COMM Fault Display communication lost
- GREEN + AMBER on LWCO light: probe service soon
- GREEN on LWCO light: normal operation
- Hardware Fault Main board RAM, ROM, or communication fault
- Hardware Fault 1,2,3,4 Gas valve output circuit fault
- MINIMUM AIR FLOW SWITCH FAULT Minimum air flow switch in wrong state
- OUTDOOR SENSOR ERROR Outdoor sensor shorted or open
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain SlimFit Series 2 boiler manual, p. 100. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.