Weil-McLain · Boiler

OUTDOOR SENSOR ERROR Outdoor sensor shorted or open

Low severity SlimFit Series 2

What the control is telling you

Outdoor temperature sensor is shorted or open. Warning only. Supply max is targeted until outdoor temperature is restored, if used for target adjustment. Auto-resets when the condition clears.

Applies to: SlimFit 1000-2000 Series 2

Likely causes

  • Shorted or open outdoor sensor
  • Loose wiring or pin engagement
  • Failed control

Test and repair steps

  1. Measure the sensor resistance and compare to Figure 90, page 94; replace the sensor if incorrect.
  2. Check the harness for loose connections and pin engagement at sensor, chassis mount, and control.
  3. Unplug sensor and control and check continuity between ends.
  4. Replace the control if the problem persists.

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Weil-McLain SlimFit Series 2 boiler manual, p. 101. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.