Weil-McLain · Boiler
OUTDOOR SENSOR ERROR Outdoor sensor shorted or open
What the control is telling you
Outdoor temperature sensor is shorted or open. Warning only. Supply max is targeted until outdoor temperature is restored, if used for target adjustment. Auto-resets when the condition clears.
Applies to: SlimFit 1000-2000 Series 2
Likely causes
- Shorted or open outdoor sensor
- Loose wiring or pin engagement
- Failed control
Test and repair steps
- Measure the sensor resistance and compare to Figure 90, page 94; replace the sensor if incorrect.
- Check the harness for loose connections and pin engagement at sensor, chassis mount, and control.
- Unplug sensor and control and check continuity between ends.
- Replace the control if the problem persists.
Other codes on the same units
- DISPLAY COMM Fault Display communication lost
- GREEN + AMBER on LWCO light: probe service soon
- GREEN on LWCO light: normal operation
- Hardware Fault Main board RAM, ROM, or communication fault
- Hardware Fault 1,2,3,4 Gas valve output circuit fault
- MINIMUM AIR FLOW SWITCH FAULT Minimum air flow switch in wrong state
- RED + AMBER LWCO light: control locked out
- RED blinking LWCO light: LWCO component failure
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain SlimFit Series 2 boiler manual, p. 101. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.