Weil-McLain · Boiler
Nothing shown on display, boiler operating Display communication lost or contrast needs adjustment
What the control is telling you
The boiler runs but the display is blank. Communication from the control to the display has been lost, or the contrast is set wrong.
Applies to: SlimFit 550/750 Series 3
Likely causes
- Loose connection at plug P9, Pump/Com board P6 and J1, or the back of the display
- Broken wire harness between display and control
- Failed display module
Test and repair steps
- Check for loose connections and pin alignment at control plug P9, Pump/Com board P6 and J1, and the display back.
- Check continuity on the wire harness from display to control.
- Cycle power using the boiler power switch.
- Look at the screen from other angles, then adjust contrast.
- Replace the display module if none of these work.
Other codes on the same units
- GREEN Low water cutoff light: normal operation
- GREEN + AMBER Low water cutoff light: service probe soon
- Hardware Fault X Gas valve output circuit problem on control
- Nothing is shown in display screen (120V) No display and no boiler components operating
- Nothing shown on display screen No display, boiler does not respond to call for heat (24V)
- PS Fault Exp. Board Pressure switch issue on expansion board
- WWSD Warm weather shut down (display status)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain SlimFit Series 3 boiler manual, p. 100. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.