Nothing is shown in display screen (120V) No display and no boiler components operating

High severity SlimFit Series 3

What the control is telling you

The control is not receiving 120 V line power.

Applies to: SlimFit 550/750 Series 3

Likely causes

  • Service switch or circuit breaker off
  • Blown 12-amp line voltage fuse
  • Wiring fault inside the control pod

Test and repair steps

  1. Make sure the service switch and circuit breaker are on.
  2. Check for 120 VAC at the service switch; if absent, fix the supply.
  3. Check for 120 VAC at the line voltage terminal block inside the top left electrical compartment.
  4. Inspect the 12-amp fuse and replace with the specified part if needed. If it blows again, recheck the wiring.

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Weil-McLain SlimFit Series 3 boiler manual, p. 100. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.