Weil-McLain · Boiler
Nothing shown on display screen No display, boiler does not respond to call for heat (24V)
What the control is telling you
The control is not receiving 24 V power, so the display stays blank and the boiler will not start.
Applies to: SlimFit 550/750 Series 3
Likely causes
- Short circuit or incorrect wiring
- Blown 3-amp low voltage fuse
- Transformer not outputting 24 VAC
Test and repair steps
- Correct wiring per the wiring diagram, including the transformer connection to the control.
- Check the 3-amp low voltage fuse and replace with the specified part if blown. If it blows again, recheck the wiring.
- Check the transformer connection and 24 V output. Replace the transformer if it gets 120 VAC but gives no 24 VAC.
Other codes on the same units
- GREEN Low water cutoff light: normal operation
- GREEN + AMBER Low water cutoff light: service probe soon
- Hardware Fault X Gas valve output circuit problem on control
- Nothing is shown in display screen (120V) No display and no boiler components operating
- Nothing shown on display, boiler operating Display communication lost or contrast needs adjustment
- PS Fault Exp. Board Pressure switch issue on expansion board
- WWSD Warm weather shut down (display status)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain SlimFit Series 3 boiler manual, p. 100. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.