Weil-McLain · Boiler
GREEN Low water cutoff light: normal operation
What the display is showing
Green light on means the low water cutoff is operating normally.
Applies to: SlimFit 550/750 Series 3 low water cutoff
Other codes on the same units
- GREEN + AMBER Low water cutoff light: service probe soon
- Hardware Fault X Gas valve output circuit problem on control
- Nothing is shown in display screen (120V) No display and no boiler components operating
- Nothing shown on display screen No display, boiler does not respond to call for heat (24V)
- Nothing shown on display, boiler operating Display communication lost or contrast needs adjustment
- PS Fault Exp. Board Pressure switch issue on expansion board
- WWSD Warm weather shut down (display status)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain SlimFit Series 3 boiler manual, p. 101. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.