Weil-McLain · Boiler
DISPLAY COMM Fault Display communication lost
What the control is telling you
Display has lost communication with the control for 30 seconds. Clears automatically when communication returns.
Applies to: SlimFit 1000-2000 Series 2
Likely causes
- Loose connection at control molex plug or back of display
- Faulty display wire harness
- Failed display module
Test and repair steps
- Check the molex plug on the control and the connection on the back of the display for looseness.
- Check continuity of the harness between display and control.
- Cycle boiler power and check operation.
- Replace display module if fault persists.
Other codes on the same units
- AIR PRESSURE Switch Open Air pressure switch open
- Closure Switch Fault Closure switch open on P7 pins 2 and 3
- GREEN + AMBER on LWCO light: probe service soon
- GREEN on LWCO light: normal operation
- Hardware Fault Main board RAM, ROM, or communication fault
- Hardware Fault 1,2,3,4 Gas valve output circuit fault
- MINIMUM AIR FLOW SWITCH FAULT Minimum air flow switch in wrong state
- OUTDOOR SENSOR ERROR Outdoor sensor shorted or open
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain SlimFit Series 2 boiler manual, p. 97. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.