Weil-McLain · Boiler

DISPLAY COMM Fault Display communication lost

Medium severity SlimFit Series 2

What the control is telling you

Display has lost communication with the control for 30 seconds. Clears automatically when communication returns.

Applies to: SlimFit 1000-2000 Series 2

Likely causes

  • Loose connection at control molex plug or back of display
  • Faulty display wire harness
  • Failed display module

Test and repair steps

  1. Check the molex plug on the control and the connection on the back of the display for looseness.
  2. Check continuity of the harness between display and control.
  3. Cycle boiler power and check operation.
  4. Replace display module if fault persists.

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Weil-McLain SlimFit Series 2 boiler manual, p. 97. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.