Weil-McLain · Boiler

Closure Switch Fault Closure switch open on P7 pins 2 and 3

Medium severity SlimFit Series 2

What the control is telling you

Closure switch connections on P7 pins 2 and 3 have been open for more than 4 minutes. Soft lockout when the 4 minute timer expires; resets when closure is made.

Applies to: SlimFit 1000-2000 Series 2

Likely causes

  • Jumper missing or on wrong pins
  • Flow switch wiring or pump problem
  • Damper not opening (CAD)

Test and repair steps

  1. If no device is attached, check the jumper is on the correct pins and secure.
  2. If a flow switch is attached, check the correct pump is on, check wiring to the flow switch, and confirm the switch closes.
  3. If a CAD is used, check voltage to the damper and confirm it opens.

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Weil-McLain SlimFit Series 2 boiler manual, p. 101. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.