Weil-McLain · Boiler
MINIMUM AIR FLOW SWITCH FAULT Minimum air flow switch in wrong state
What the control is telling you
Minimum air flow switch is open when it should be closed, or closed when it should be open. Switch should close when the blower moves enough air. Manual reset required.
Applies to: SlimFit 1000-2000 Series 2
Likely causes
- Blower not running correctly
- Switch stuck open or closed
- Damaged or disconnected hose
- Loose or damaged wiring
- Combustion Air Pressure Kit installed
- Sense line connection problem
Test and repair steps
- Check the blower is operating correctly.
- Check that the switch is not stuck open or closed.
- Check the hose connection to the switch for disconnection or damage.
- Check wiring connections are firm and undamaged.
- Check whether a Combustion Air Pressure Kit has been installed.
- Check sense line connections and electrical wiring.
Other codes on the same units
- DISPLAY COMM Fault Display communication lost
- GREEN + AMBER on LWCO light: probe service soon
- GREEN on LWCO light: normal operation
- Hardware Fault Main board RAM, ROM, or communication fault
- Hardware Fault 1,2,3,4 Gas valve output circuit fault
- OUTDOOR SENSOR ERROR Outdoor sensor shorted or open
- RED + AMBER LWCO light: control locked out
- RED blinking LWCO light: LWCO component failure
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain SlimFit Series 2 boiler manual, p. 101. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.