Viessmann · Heat pump

E70 IPM overheat

High severity Vitocal 100-AW AM2V

What the control is telling you

The power module (IPM) on the fan driver board is overheating. Usually the fan is not turning and draws high current, or the thermal grease under the module is insufficient.

Applies to: Outdoor unit

Likely causes

  • Fan does not rotate and current is high
  • Too little thermally conductive silicone grease under the module

Test and repair steps

  1. Check that the fan runs normally.
  2. Check the thermal grease on the fan driver board heat sink for uneven spread or missing grease.
  3. Repair the fan or fan driver board as needed.
  4. Remove the old grease and re-apply thermal grease so all gaps are filled.

Other codes on the same units

  • E71 Compressor start failure
  • E72 Compressor overcurrent (manual reset required)
  • E73 Input voltage phase loss
  • E74 IPM current sampling fault
  • E75 Overheat protection of drive board devices
  • E76 Pre-charge failure
  • E77 DC bus over voltage
  • E78 DC bus under voltage

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 81. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.