Viessmann · Heat pump

E78 DC bus under voltage

High severity Vitocal 100-AW AM2V

What the control is telling you

DC bus voltage is too low, from supply voltage or a faulty sampling circuit.

Applies to: Outdoor unit

Likely causes

  • Input voltage too low
  • Sampling circuit damaged

Test and repair steps

  1. Check whether the input voltage is too low.
  2. If readings are normal and the fault returns after power-off, power-on and restart, replace the driver board.
  3. Fix the grid problem before restarting.
  4. Replace the inverter board if the fault remains after restarting.

Other codes on the same units

  • E74 IPM current sampling fault
  • E75 Overheat protection of drive board devices
  • E76 Pre-charge failure
  • E77 DC bus over voltage
  • E79 AC input voltage under voltage
  • E80 IPM overheat stop
  • E81 - E82 Reserved
  • E83 15 VDC under voltage

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 82. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.