Viessmann · Heat pump
E80 IPM overheat stop
What the control is telling you
The IPM on the fan driver board has stopped the unit for overheating. Usually the fan is not turning and draws high current, or the thermal grease is insufficient.
Applies to: Outdoor unit
Likely causes
- Fan does not rotate and current is high
- Too little thermally conductive silicone grease under the module
Test and repair steps
- Check that the fan runs normally.
- Check the thermal grease on the fan driver board heat sink for uneven spread or missing grease.
- Repair the fan or fan driver board as needed.
- Remove the old grease and re-apply thermal grease so all gaps are filled.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 83. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.