Viessmann · Heat pump

E76 Pre-charge failure

Medium severity Vitocal 100-AW AM2V

What the control is telling you

The pre-charge stage failed, from input phase loss or from repeated power cycling that overheats the PTC.

Applies to: Outdoor unit

Likely causes

  • Input phase loss
  • Power applied after a power failure without full discharge, or frequent on/off cycling overheating the PTC

Test and repair steps

  1. Check the input terminal connections on the driver board and the supply.
  2. Wait 5 minutes after a power loss before powering up again.
  3. Tighten the input terminal connections on the driver board and supply.

Other codes on the same units

  • E72 Compressor overcurrent (manual reset required)
  • E73 Input voltage phase loss
  • E74 IPM current sampling fault
  • E75 Overheat protection of drive board devices
  • E77 DC bus over voltage
  • E78 DC bus under voltage
  • E79 AC input voltage under voltage
  • E80 IPM overheat stop

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 82. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.