E73 Input voltage phase loss
What the control is telling you
A phase of the input supply is missing at the driver.
Applies to: Outdoor unit
Likely causes
- Incorrect input terminal connection
- Fuse damaged and driver damaged
Test and repair steps
- Check the input terminal connections for correct wiring and poor contact.
- With a meter, check whether the fuse is open. If so, replace it.
- If everything else is OK, replace the driver board.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 82. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.