E71 Compressor start failure
What the control is telling you
The compressor failed to start.
Applies to: Outdoor unit
Likely causes
- EEV step, high pressure, low pressure or inlet/outlet water temperature out of normal range
- Compressor U/V/W connections to the driver board faulty
- Compressor resistance abnormal
- Compressor driver board faulty
Test and repair steps
- Check the EEV step, high and low pressures, and inlet/outlet water temperatures.
- Check the U/V/W connections between compressor and compressor driver board.
- Check compressor resistance.
- Check the compressor driver board.
- Restart the unit.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 81. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.