Viessmann · Heat pump
E72 Compressor overcurrent (manual reset required)
What the control is telling you
Compressor current is too high. The current detection circuit may be faulty, or the compressor load is too high.
Applies to: Outdoor unit
Likely causes
- Current detection module damaged
- Compressor load too large
Test and repair steps
- Read the displayed compressor current T36 and compare it with a clamp meter reading on the compressor. If the error is out of range, the inverter board current detection is faulty.
- With a meter on ohms, check resistance between UV, UW and VW. Normal is 1 to 20 ohms and roughly equal per phase. If out of range, the compressor is damaged.
- Check other temperature and pressure values to find the system cause of overcurrent.
- Replace the inverter board or the compressor as indicated.
- Reset shut off the outdoor unit breaker and turn it back on.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 81. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.