Viessmann · Heat pump

E72 Compressor overcurrent (manual reset required)

High severity Vitocal 100-AW AM2V

What the control is telling you

Compressor current is too high. The current detection circuit may be faulty, or the compressor load is too high.

Applies to: Outdoor unit

Likely causes

  • Current detection module damaged
  • Compressor load too large

Test and repair steps

  1. Read the displayed compressor current T36 and compare it with a clamp meter reading on the compressor. If the error is out of range, the inverter board current detection is faulty.
  2. With a meter on ohms, check resistance between UV, UW and VW. Normal is 1 to 20 ohms and roughly equal per phase. If out of range, the compressor is damaged.
  3. Check other temperature and pressure values to find the system cause of overcurrent.
  4. Replace the inverter board or the compressor as indicated.
  5. Reset shut off the outdoor unit breaker and turn it back on.

Other codes on the same units

  • E70 IPM overheat
  • E71 Compressor start failure
  • E73 Input voltage phase loss
  • E74 IPM current sampling fault
  • E75 Overheat protection of drive board devices
  • E76 Pre-charge failure
  • E77 DC bus over voltage
  • E78 DC bus under voltage

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 81. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.