E082 Right product water solenoid valve opening
What the control is telling you
Right product water solenoid valve opening fault. Check whether water flows to the drain when the faucet is opened.
Applies to: WEC600
Likely causes
- Faulty product water solenoid valve or harness
- Faulty flow sensor or harness
Test and repair steps
- Open the faucet and check whether water flows to the drain.
- If water flows to the drain, replace the corresponding drain line product water solenoid valve or its harness.
- If not, replace the flow sensor or its harness.
- Reset the error.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien WEC service manual, p. 67. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.