Navien · General

E083 CIP dosing pump fault

Medium severity WEC Series

What the control is telling you

Fault in the CIP dosing system during Install Check Mode. Check CIP solution injection from State 33.

Applies to: WEC600

Likely causes

  • Low CIP solution in tank
  • Air in CIP line
  • Faulty CIP dosing pump or harness
  • Faulty TDS sensor or harness

Test and repair steps

  1. Check the remaining amount of CIP solution in the tank.
  2. If air is in the CIP line, reset the error and restart CIP.
  3. If the error returns, check whether the CIP dosing pump runs correctly and the CIP solution injection from State 33 is visible.
  4. If the pump is not operating correctly, replace the CIP dosing pump or its harness.
  5. If the pump operates correctly, replace the TDS sensor or its harness.

Other codes on the same units

  • E079 Left drain regeneration line opening
  • E080 Right drain regeneration line opening
  • E081 Left product water solenoid valve opening
  • E082 Right product water solenoid valve opening
  • E084 Circulation pump fault
  • E090 - E100 Individual sensor or pump fault
  • E105 PCB fault
  • E106 PCB or harness fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien WEC service manual, p. 68. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.